ServerTech CDUs are smart power supplies with support for power and environmental monitoring, and (some models) outlet control.

Issues

  • After ANY IP/Network/SNMP/syslog changes, the settings must be saved and the PDU/CDU restarted. Restarting the PDU/CDU does NOT interrupt power delivery, and all powered gear should remain unaffected.

Initial Setup

  • connect the PDU to it's serial connection, then connect and login to the PDU via serial
    • default user/pass is admn/admn
  • immediately run the following to set the ip info so you can connect via HTTPS to configure the remainder (example is for PDUs in eqiad, you'll need to change for your site's network info):

set dhcp disabled set ipv4 address <ip address> set ipv4 gateway 10.65.0.1 set ipv4 subnet 255.255.0.0 set dns primary 10.3.0.1 set dns secondary 10.3.0.1 reboot

  • Confirm reboot, you should now be able to connect to the device via https://ps1-rack-site.mgmt.site.wmnet to setup the remainder
  • Connect via https and login with the default admn/admn, we'll change this first.
  • Go to Configuration > Access > Local Users >
    • Create Users and create the root user, using the mgmt-pdu password.
    • Edit the root user, and change Access Level to Administrator
  • Log out, and log back in as root
  • Go to Configuration > Access > Local Users >
    • Delete the default admn user.
  • Go to Configuration > Network > DHCP/IP
    • Configure DHCP settings to set the FQDN to the pdu FQDN
    • Un-check Zero Touch Provisioning
    • Apply Settings (don't reboot yet, we'll do that when we are done)
  • Go to Configuration > Network > HTTP/HTTPS
    • Un-check Enable under HTTP server (because unsecured traffic is a bad idea)
    • Apply Settings (don't reboot yet, we'll do that when we are done)
  • Go to Configuration > Network > SNMP
    • Set the SNMPv2 Agent GET and SET passwords (you should copy this from another PDU)
    • Set the system name (FQDN)
    • Set the system location (site)
    • Set system contact: Wikimedia <noc@wikimedia.org>
    • Apply Settings (don't reboot yet, we'll do that when we are done)
  • Go to Configuration > Network > SMTP
    • Set primary and secondary hosts (depending on which is closest site to PDU) as ntp.eqiad.wikimedia.org and ntp.codfw.wikimedia.org
    • Apply Settings (don't reboot yet, we'll do that when we are done)
  • Go to Configuration > Network > Syslog
    • Set both Host 1 and Host 2 to syslog.anycast.wmnet
    • Apply Settings
  • Now we will reboot the PDU for it to apply the above, go to Tools > Restart > Action : Restart and Apply.
  • PDU will restart and apply all the updated settings, should immediately start showing in librenms.

Adding items to scs

  • using a browser go to the scs example:scs-a1-sdtpda.mgmt.pmtpa.wmnet
  • add the pdu to the appropriate port
  • connect the pdu to the scs switch (be sure to use cisco wire cfg)
  • From terminal go to root@scs-a1-sdtpa.mgmt connect to the port using commands
  • #pmshell
  • #“port #”
  • Run the following commands be sure to set the ip address to the appropriate ip address
  • set dhcp disabled
  • set ipaddress “10.1.5.21”
  • set subnet 255.255.0.0
  • set gateway “10.1.0.1”
  • restart

After the pdu restarts

  • Using a web browser go to the web page and accept the security certificate (you can use the IP Adress in the address bar)
  • Login to the pdu with the default user/passwd admn/admn
  • Go to users and create user "root" and give it the management password. Then click apply
  • Under the action link use edit and select admin as the role and click apply.
  • Logout of the pdu and then login again as user: root with the mgmt password
  • go to users and delete the admn user.

Setting up the Configuration

Configuration:
	System:
		About:
			Location: ulsfo
		Bluetooth:
			Enable unchecked

	Network:
		DHCP/IP:
			Primary DNS:  10.3.0.1
			IPv4 Address/mask/gateway: SET
			FQDN: SET
			DHCP: Uncheck
		FTP:
			FTP Server: Uncheck*
		HTTP/HTPS:
			HTTP Server: Uncheck*
			HTTPS server: Verify Checked
		SNMP:
			SNMPv2 Agent: Enable
			GET Community: Set to SNMP secret*
			SET Community: Empty
			System Name: Set to hostname
			System Location: Set to site code (ulsfo, etc.)
			System Contact: noc@wikimedia.org
		SNTP:
			Primary host: ntp.eqiad.wikimedia.org
			Secondary host: ntp.codfw.wikimedia.org
		Syslog:
			Host 1: syslog.anycast.wmnet
		Telnet/SSH:
			Telnet server: Uncheck*
			SSH server: verify checked
	Access:
		Local Users:
			admn: remove
Tools:
	restart:
		Action: Restart


* Restart required

Adding devices to monitoring

Add device to LibreNMS: LibreNMS#Add a device to LibreNMS

Add device to Icinga: duplicate this change

Other Info

powering off and on outlets

These instructions are good for Sentry Switched CDU 6.0 firmware. (Manuals here, see the manuals for Firmware Version 6.0). They may well work for other versions of the firmware but haven't been tested there.

Please Note: We have a very limited number of switched powerstrips in place. Only the network racks (A1-sdtpa, A1-eqiad, A8-eqiad) and B1-sdtpa have these. The rest have normal non-switched powerstrips. The reasoning behind this is that the switched strip has more parts and complexity and can have issues more easily than the more simple strips. Networking kit does not normally have full out of band lights management, so those racks have them. B1-sdtpa is a legacy rack to have older servers that do not have full lights out management remote reboot capabilities.

  1. Find the pdu for your rack and your server. See Netbox
    It will have a name like ps1-b1-sdtpa.mgmt.pmtpa.wmnet (powerstrip-n, rack m, dc name...)
  2. ssh in, use standard credentials for the manangement network.
  3. Check what outlets or groups of outlets you want. You can list those by:
    list user
    At the "Username:" prompt, type root. The outlets are first, the groups at the bottom.
  4. To power the outlet off, do
    off name-of-outlet-or-group-here
    Example: off .BC6 or off dataset1-all
  5. To power the outlet on, do
    on name-of-outlet-or-group-here

Sample successful output from a power off command:

Switched CDU: off dataset1-all

   Group: dataset1-all

   Outlet   Outlet                    Outlet     Load      Power     Control
   ID       Name                      Status     (Amps)    (Watts)   State

   .AC6     dataset1_a:xz:6           Off        0.00      0         Off       
   .AC7     dataset1-array1_z:xz:7    Off        0.00      0         Off       
   .BC6     dataset1_b:xz:6           Off        0.00      0         Off       
   .BC7     dataset1-array1_b:xz:7    Off        0.00      0         Off       

   Command successful

Switched CDU:

Power on gives similar results.

Note that there's a five minute timeout so if you idle too long you'll have to reconnect.

summary of other commands

A few other useful commands:

  • From the command line, hitting return/enter will show you a list of commands it knows.
  • Check the version of the firmware by show system. It also announces the firmware version when you login.
  • Some commands for displaying various statuses: show ports/network/options/towers/infeeds/traps/system
  • A couple monitoring commands: istat, envmon, sysstat
  • Listing user info: list user (you will be prompted for a specific user), list users (you will be shown a list of all users)